Math & ScienceCopper & aluminum

Voltage Drop Calculator

Every meter of cable is a resistor you did not plan for. This works out how many volts a run loses at a given current, whether that breaches the usual 3% branch-circuit guidance, and what size conductor would fix it.

The Run

Length is one-way. The calculator doubles it for the return conductor.

V
A
ft
VOLTAGE DROP
5.93 V
Drop as a percentage4.94%
Voltage at the load114.1 V
Power lost as heat in the cable89 W (1 kWh a year if run continuously)
Against 3% branch guidanceOver 3%, within 5% (4.94%)
Smallest size that meets 3%8 AWG
12 AWG copper, 100 ft one way, 15 A, single-phase (×2 for the return): 5.93 V lost, 4.94% of 120 V, leaving 114.1 V at the load. Over the usual 3% branch-circuit target though within 5% overall. 8 AWG would bring it under 3%. This is a DC-resistance calculation at a fixed resistivity — it ignores conductor temperature rise (about 0.4% per °C for copper), AC skin effect on large conductors, and power factor. The 3% and 5% figures are common design guidance, not a universal legal limit; check your local code.

Where the formula comes from

A conductor has resistance proportional to its length and inversely proportional to its cross-sectional area. Expressed in the units the trade uses, that is Vdrop = 2 × K × I × L ÷ CM, where K is the resistivity of the metal in ohm-circular mils per foot, I is the current in amps, L is the one-way length in feet and CM is the cross-section in circular mils. K is about 12.9 for copper and 21.2 for aluminum at normal operating temperature. The factor of 2 accounts for the return conductor — current has to come back. Three-phase circuits use √3 (about 1.732) instead of 2, because the phase currents partially cancel in the neutral.

Why 3% and 5%

Those figures are recommendations, not hard limits on safety. The common guidance is no more than 3% drop on a branch circuit and no more than 5% total from the service to the furthest outlet. The reasoning is performance rather than fire risk: motors lose torque and run hotter on low voltage, incandescent lamps dim noticeably, and electronic supplies draw more current to compensate, which makes the drop worse. Local codes differ on whether these are mandatory, so treat the check here as a design target and confirm against the rules that apply to you.

Aluminum is not just cheaper

Aluminum has roughly 61% the conductivity of copper, so an aluminum conductor needs to be about two AWG sizes larger to match a copper one for drop. It is lighter and cheaper per amp delivered, which is why utility feeders use it, but it also creeps under pressure and oxidises into a non-conductive film, so terminations need rated connectors and antioxidant compound. Mixing the two metals at a terminal without a rated connector is a classic cause of hot joints.

What this calculator does not include

This is a DC-resistance calculation with a fixed resistivity. It ignores conductor temperature rise, which raises resistance by about 0.4% per °C for copper, and it ignores AC effects — skin effect and proximity effect — that begin to matter above roughly 2/0 for 60 Hz power. It also assumes a power factor of 1; a motor load with a lagging power factor produces a different drop for the same real power. For a large feeder, a design calculation should use the impedance tables for the actual cable and installation method rather than a single K value.

Fixing a failing run

There are only four levers: shorten the run, raise the voltage, lower the current, or fatten the conductor. Raising voltage is the most effective when it is available — doubling the voltage quarters the percentage drop for the same delivered power, because current halves and the drop is proportional to current. That is why long runs to outbuildings are often fed at 240 V and stepped down locally rather than run at 120 V.

Frequently Asked Questions

Is the length one-way or round trip?
One-way. Enter the distance from the source to the load and the calculator doubles it for single-phase and DC, or applies the square-root-of-three factor for three-phase.
Why does aluminum need a bigger wire?
Its resistivity is about 64% higher than copper, so for the same drop an aluminum conductor needs roughly two AWG sizes more cross-section.
Is 3% a legal limit?
It is widely used design guidance rather than a universal legal limit — commonly 3% on a branch circuit and 5% overall. Requirements vary by jurisdiction, so check the code that applies to your installation.
Does voltage drop waste energy?
Yes. The volts lost in the cable appear as heat in the conductor. The power-lost line shows that figure — it is current squared times cable resistance, and you pay for it continuously.
Where these numbers come from

Sources

Official publications only. Links open the original document in a new tab.